| TOPIC | IFC 2015 | IFC 2018 | IFC 2021 | IFC 2024 | IFC 2027 – COMING SOON |
|---|---|---|---|---|---|
| Relevant Referenced Standards – IFC Ch. 80 | NFPA 72-2013 | NFPA 72-2016 NFPA 1221-2016 |
NFPA 72-2019 NFPA 1221-2019 |
NFPA 72-2022 NFPA 1225-2022 |
|
| Approved Emergency Services Department Communications Required | Sec. 510.1, 510.2 | Sec. 510.1, 510.2 | Sec. 510.1, 510.2 | Sec. 510.1 , 510.2 Note: Exception 4 One Story Buildings less than 12,000 Sq. Ft. |
|
| Field testing – Building Signal Coverage Assessment Required | 510.6.3 | 510.6.4 | 510.6.4 | 510.6.4 | |
| Permit Required | Section 510.3 | Section 510.3 | Section 510.3 | Section 510.3 | |
| Listing of Equipment | Not Specifically Addressed in Section 510 | Not Specifically Addressed in Section 510 | Sec. 510.4 – Listed to UL 2524 | Sec. 510.4 – Listed to UL 2524 | |
| Limitation of External References | Not specifically addressed | Not specifically addressed | Not specifically addressed | Not specifically addressed | |
| Signal Strength and Quality & Area Coverage Required |
-95 dBm Sec. 510.4.1.1 & 510.4.1.2 95% General – Sec. 510.4.1 99% Critical – Not Specifically Addressed in Sec. 510 |
DAQ 3.0 Sec. 510.4.1.1 95% General – Sec. 510.4.1 99% Critical – Not Specifically Addressed in Sec. 510 |
-95 dBm & DAQ 3.0 Sec. 510.4.1.1 95% General – Sec. 510.4.1 99% Critical – Sec. 510.4.1 |
DAQ 3.0 Sec. 510.4.1.1 95% General – Sec. 510.4.1 99% Critical – Sec. 510.4.1 |
|
| IFC reference to NFPA 1221 or 1225 Standards | No | Sec. 510.4.2 & 510.5 Reference to NFPA 1221-2016 | Sec. 510.4.2 & 510.5 Reference to NFPA 1221-2019 | Sec. 510.4.2 & 510.5 Reference to NFPA 1225-2022 | |
| Backbone / Riser Cable Defined | Not Defined | Not Defined | Refers to NFPA 1221-2019 | Refers to NFPA 1225-2022 | |
| Distribution / Feeder Cable Defined | Not Defined | Not Defined | Refers to NFPA 1221-2019 | Refers to NFPA 1225-2022 | |
| Pathway Survivability: Fire Rating | Not Specifically Addressed in Section 510. Referenced in 2013 NFPA 72 Section 24.3.6.8 |
Where Required in NFPA 1221-2016 Note: Also See NFPA 1221 TIA 16-2 |
Where Required in NFPA 1221-2019 | Where Required in NFPA 1225-2022 | |
| Pathway Survivability: Mechanical Protection | Not Specifically Addressed in Section 510. Referenced in 2013 NFPA 72 Section 24.3.6.8 |
Where Required in NFPA 1221-2016 | Where Required in NFPA 1221-2019 | Where Required in NFPA 1225-2022 | |
| Plenum Rated Coaxial Cable Required | Not Specifically Addressed in Section 510. Referenced in 2013 NFPA 72 Section 24.3.6.8 |
Where Required in NFPA 1221-2016 | Where Required in NFPA 1221-2019 | Where Required in NFPA 1225-2022 | |
| Lightning Protection Required | Not Specifically Addressed in Section 510 | Where Required in NFPA 1221-2016 | Where Required in NFPA 1221-2019 | Where Required in NFPA 1225-2022 | |
| Noise Floor Requirement | Not Specifically Addressed in Section 510 | Not Specifically Addressed in Section 510 | Not Specifically Addressed in Section 510 | Sec. 510.4.2.9 Also see NFPA 1225-2022 Sec. 18.9.3 |
|
| Technical Criteria to be Provided by AHJ(s) | 510.4.2.2 | 510.4.2.2 | 510.4.2.2 | 510.4.2.2 | |
| Standby Power | 24 Hours – Sec. 510.4.2.3 | 12 Hours – Sec. 510.4.2.3 or 2-Hours Battery w/ Emergency Generator |
12 Hours – Sec. 510.4.2.3 or 2-Hours Battery w/ Emergency Generator |
12 Hours – Sec. 510.4.2.3 or 2-Hours Battery w/ Emergency Generator |
|
| Isolation of Donor Antenna Required | Not Specifically Addressed in Sec. 510 | 20db – Sec. 510.4.2.4(4) | 20 db Above System Gain – Sec. 510.4.2.4(4) | 20 db Above System Gain – Sec. 510.4.2.4(4) | |
| Cabinets for Equipment and Battery Backup Required | NEMA 4 – Sec. 510.4.2.4 (1) & (2) | NEMA 4/NEMA 3R – Sec. 510.4.2.4 (1) & (2) | NEMA 4/NEMA 3R – Sec. 510.4.2.4 (1) & (2) | NEMA 4/NEMA 3R – Sec. 510.4.2.4 (1) & (2) | |
| Frequency License Holder Approval Required | Yes under FCC Part 90.219 Referenced in Sec. 510.4 | Yes under FCC Part 90.219 Referenced in Sec. 510.4 | Yes under FCC Part 90.219 Referenced in Sec. 510.5 | Yes – Fire Code Official & Frequency License Holder Sec. 510.5.2 & 510.5.2.1 FCC Part 90.219 – Sec. 510.5.5 |
|
| Oscillation Prevention | 510.5.3 | 510.4.2.4 | 510.4.2.4 | 510.4.2.4 | |
| Monitoring By Fire Alarm Required | 510.4.2.4 | Yes – Sec. 510.4.2.5 | Yes – Sec. 510.4.2.5 | Yes – Sec. 510.4.2.5 | |
| Monitor Signal Source Malfunction Required | Not Specifically Addressed in Section 510 | Donor Antenna – Sec. 510.4.2.5 | Donor Antenna – Sec. 510.4.2.5 | Signal Source – Sec. 510.4.2.5 | |
| Dedicated Annunciation Required | Where approved by Fire Code Official: 510.4.2.4 | Where approved by Fire Code Official: 510.4.2.5 | Where approved by Fire Code Official: 510.4.2.5 | Where approved by Fire Code Official: 510.4.2.5 | |
| Additional Frequencies (May Include cellular and new technologies) | Sec. 510.6.2 Additional Frequencies Made Available by FCC | Sec. 510.6.2 Additional Frequencies Made Available by FCC | Sec. 510.6.2 Additional Frequencies Made Available by FCC | Sec. 510.4.2.6 & 510.6.2 Also see NFPA 1225-2022 A.3.3.63 |
|
| Design Documents | Not Specifically Addressed in Section 510 | 510.4.2.7 | 510.4.2.7 | 510.4.2.7 | |
| Communication Antenna Density/Near Far | Not Specifically Addressed in Section 510 | Sec. 510.4.2.8 | Sec. 510.4.2.8 | Sec. 510.4.2.8 | |
| Mounting of Donor Antenna | Not Specifically Addressed in Section 510 | Not Specifically Addressed in Section 510 | Sec. 510.5.1 | Sec. 510.5.1 | |
| Approval prior to installation | 510.5.1 | 510.5.1 | 510.5.2 | 510.5.2 | |
| Minimum qualifications of personnel | 510.5.2 | 510.5.2 | 510.5.3 | 510.5.3 | |
| System Testing – Initial, Acceptance, Annual, 5-year | New/Acceptance, Sec. 510.5.3 Annual Sec 510.6.1 |
New/Acceptance, Sec. 510.5.3 Annual Sec 510.6.1 |
New Systems Sec. 510.5.4 Annual – Section 510.6.1 |
New Systems Sec. 510.5.4 Annual – Section 510.6.1 |
|
| Compliance with FCC Part 90.219 | Sec. 510.5.4 | Sec. 510.5.4 | Sec. 510.5.5 | Sec. 510.5.5 | |
| Responsibility to Prevent or Correct Interference with Public Safety System | By reference: 510.5.4 FCC compliance | By reference: 510.5.4 FCC compliance | By reference: 510.5.5 FCC compliance | By reference: 510.5.5 FCC compliance | |
| Nonpublic safety system – non-interference | Not Specifically Addressed in Section 510 | 510.6.3 | 510.6.3 | 510.6.3 |
| TOPIC | NFPA 72-2013 | NFPA 1221-2016 | NFPA 1221 – 2019 | NFPA 1225 – 2022 | NFPA 1225 – 2027 – COMING SOON |
|---|---|---|---|---|---|
| Relevant Referenced Publications – Ch. 2 | NFPA 13-2013 NFPA 101-2012 NFPA 70-2011 |
NFPA 1-2015 NFPA 13-2016 NFPA 101-2015 NFPA 70-2014 NFPA 72-2016 NFPA 780-2014 |
NFPA 1-2018 NFPA 13-2019 NFPA 101-2018 NFPA 70-2017 NFPA 72-2019 NFPA 780-2017 |
NFPA 1-2021 NFPA 13-2022 NFPA 101-2021 NFPA 70-2020 NFPA 72-2022 NFPA 780-2020 |
|
| Approved Emergency Services Department Communications Required | NFPA 1 Section 11.10 | NFPA 1 Section 11.10 | NFPA 1 Section 11.10 | NFPA 1 Section 11.10 | |
| Field testing – Building Signal Coverage Assessment Required | NFPA 1 Section 11.10 | NFPA 1 Section 11.10 | NFPA 1 Section 11.10 | NFPA 1 Section 11.10 | |
| Permit Required | Section 24.5.2.1.2 | Section 9.6.6 | Section 9.6.6 | Section 18.7 | |
| Listing of Equipment | Not Specifically Addressed | Not Specifically Addressed | Specific Listing Requirement is TBD by the AHJ | Sec. 18.12.1.3 | |
| Limitation of External References | Not specifically addressed | Not specifically addressed | Not specifically addressed | 18.1.2 | |
| Signal Strength and Quality & Area Coverage Required |
-95 dBm Sec. 24.5.2.3 90% General – Sec. 24.5.2.2.2 99% Critical – Sec. 24.5.2.2.1 |
DAQ 3.0 Sec. 9.6.8 90% General – Sec. 9.6.7.5 99% Critical – Sec. 9.6.7.4 |
DAQ 3.0 9.6.8 90% General – Sec. 9.6.7.4 99% Critical – Sec. 9.6.7.3 |
DAQ 3.0 Sec. 18.9 95% General – Sec. 18.8.4 99% Critical – Sec. 18.8.3 |
|
| IFC reference to NFPA 1221 or 1225 Standards | N/A | N/A | N/A | N/A | |
| Backbone / Riser Cable Defined | Not Defined | Not Defined | 3.3.10 | 3.3.10 | |
| Distribution / Feeder Cable Defined | Not Defined | Not Defined | 3.3.46 | 3.3.49 | |
| Pathway Survivability: Fire Rating | 2 Hour for Riser Coaxial Cable – Sec. 24.3.6.8 | 2 Hour for Riser Coaxial Cable – Sec. 9.6.2.1.3 | Backbone Cable Routed Through Enclosure Matching Bldgs. Fire Rating – Sec. 9.6.2.3 |
Sections 18.12.3.1, 18.12.3.3, 18.12.3.4, 18.12.3.5, & 18.12.3.6 | |
| Pathway Survivability: Mechanical Protection | Section 24.3.6.8 | Levels DEFINED in Sec. 5.10 & 9.6.2 But REQUIREMENTS should be based upon NEC (NFPA 70-2014) |
Backbone Cable Enclosure – Sec. 9.6.2.3 Mechanical Protection per NEC (NFPA 70-2017) |
18.12.3.2 Refers to NEC (NFPA 70-2020) | |
| Plenum Rated Coaxial Cable Required | Riser & Feeder Coaxial Cable – Sec. 24.3.6.8 | Riser & Feeder Coaxial Cable – Sec. 9.6.2.1.1 | Backbone & Distribution Antenna Cables Sec. 9.6.2.1 |
Backbone & Distribution Antenna Cables Sec. 18.12.3.1 |
|
| Lightning Protection Required | Not Addressed in Section 24.5.2 | Sec. 9.6.3 – Installed per NFPA 780-2014 | Sec. 9.6.3 – Installed per NFPA 780-2017 | Sec. 18.4 – Refers to Article 820 of NFPA 70-2020. Antenna discharge units shall be listed to UL 497C | |
| Noise Floor Requirement | Not Specifically Addressed | Not Specifically Addressed | Not Specifically Addressed | Sec. 18.9.3 | |
| Technical Criteria to be Provided by AHJ(s) | 24.5.2.7 | 9.6.14 | 9.6.14 | Sec. 18.15 | |
| Standby Power | 12 Hours – Sec. 24.5.2.5.5.2 | 12 Hours – Sec. 9.6.12.2 | 12 Hours Battery or AHJ-Approved Alternative – Sec. 9.6.12.2 | 12 Hours Battery or Generator – Sec.18.13.2 | |
| Isolation of Donor Antenna Required | 15 db Above Signal Booster Gain – Sec. 24.5.2.3.3 | 20db – Sec. 9.6.9 | 20 db Above System Gain – Sec. 9.6.9 | Sec. 18.3.3.2 & 18.10 | |
| Cabinets for Equipment and Battery Backup Required | NEMA 4/NEMA 4X – Sec. 24.5.2.5.2 | NEMA 4/NEMA 4X – Sec. 9.6.11.2 | NEMA 4/NEMA 4X & NEMA 3R for Batteries – Sec. 9.6.11.2 | NEMA 4/NEMA 4X Batteries – NEMA 3R – Sec. 18.3.1 |
|
| Frequency License Holder Approval Required | Standard Requires AHJ Approval Only – Sec. 24.5.2.1.1 License Holder Consent Req. by FCC Part 90.219 |
Standard Requires AHJ Approval Only – Sec. 9.6.5.1 License Holder Consent Req. by FCC Part 90.219 |
Sec. 9.6.2, 9.6.5.1, 9.6.6.1 & 9.6.6.2 | Sections 18.2.1, 18.7 & 18.12.1.1 | |
| Oscillation Prevention | Not Specifically Addressed | Not Specifically Addressed | Not Specifically Addressed | 18.3.2 | |
| Monitoring By Fire Alarm Required | Yes – Sec. 24.5.2.6 | Yes – Sec. 9.6.13 | Sec. 9.6.13 & Chapter 10 of NFPA 72-2019 | Sec. 18.14 & Chapter 10 of NFPA 72-2022 | |
| Monitor Signal Source Malfunction Required | Donor Antenna – Sec. 24.5.2.6(2)(a) | Donor Antenna – Sec. 9.6.13.1(2)(a) | Donor Antenna – Sec. 9.6.13.2.1(5) | Sec. 18.14.1.2(2)(a) | |
| Dedicated Annunciation Required | Occupancies that require a Fire Command Center: 24.5.2.6.2 | Occupancies that require a Fire Command Center: 9.6.13.2 | Occupancies that require a Fire Command Center: 9.6.13.2.1 | Occupancies that require a Fire Command Center: 18.14.2.1 | |
| Additional Frequencies (May Include cellular and new technologies) | All assigned frequencies & any modulation technology Sec. 24.5.2.4 |
All assigned frequencies & any modulation technology Sec. 9.6.10 |
All assigned frequencies & any modulation technology Sec. 9.6.10 |
All assigned frequencies & any modulation technology Sec. 18.11 |
|
| Design Documents | 24.5.2.1.2 | Plans Submitted for Approval – Sec. 9.6.6.1 | Plans Submitted for Approval – Sec. 9.6.6.1 | 18.7.1 | |
| Communication Antenna Density/Near Far | Not Specifically Addressed | Not Specifically Addressed | Sec. 9.6.7.6 | Sec. 18.3.4 | |
| Mounting of Donor Antenna | Not Specifically Addressed | Not Specifically Addressed | Not Specifically Addressed | Sec. 18.3.3 | |
| Approval prior to installation | 24.5.2.1.2 | 9.6.6.1 | 9.6.2 | 18.2, A.18.2.1 | |
| Minimum qualifications of personnel | Not Specifically Addressed | Not Specifically Addressed | Not Specifically Addressed | 18.2 and 3.3.115, Annex: A.3.3.115 |
|
| System Testing – Initial, Acceptance, Annual, 5-year | Sec. 24.5.2.1.2 & 14.4.10 | Sec. 9.6.4, 11.3.9 & 11.3.9.1 | Sec. 9.6.4, 11.3.9 & 11.3.9.1 | 18.5 & Section 20.3.10.1, See Annex | |
| Compliance with FCC Part 90.219 | Not Specifically Listed in the Standard, Required by Federal Law | Not Specifically Listed in the Standard, Required by Federal Law | Not Specifically Listed in the Standard, Required by Federal Law | Sec. 18.7.2 & A.18.7.2 Also Req. Under FCC Rules in the US |
|
| Responsibility to Prevent or Correct Interference with Public Safety System | 24.5.2.1.1 | 9.6.5 | 9.6.5 | 18.6 | |
| Nonpublic safety system – non-interference | 24.5.2.1.1 | 9.6.5 | 9.6.5 | 18.6 |